Evaluation of Voltage Profile in ETAP (Electric Transient And Analysis Program) at Ahuru Feeder 20 kV Medium Voltage Distriution

  • Marceau A. F. Haurissa Department Electrical Engineering, Ambon State Polytechnic, Ambon, Indonesia
  • Marselin Jamlaay Department Electrical Engineering, Ambon State Polytechnic, Ambon, Indonesia
  • Lory M. Parera Department Electrical Engineering, Ambon State Polytechnic, Ambon, Indonesia
Keywords: Voltage profile; losses; feeder; medium voltage 20 kV and ETAP.

Abstract

Ahuru feeder is the feeder with the longest network of all Ambon city distribution networks. So it is predicted that losses will occur in the network because the longer the distribution channel, the greater the voltage drop. Voltage drops in the network cause energy losses (losses) which need to be evaluated and anticipated whether they occur within normal and reasonable limits. So in this research an evaluation of the voltage profile of the Ahuru feeder was carried out using the power flow analysis method using ETAP 12.6.0 software. Based on the simulation results, under installed load conditions, there is a voltage drop below the PLN standard on the BusL-ERIE3 line of 18.99kV or 95% up to the end of the BusL-WAYOMAR series network of 18.907kV or 94.5% of the nominal voltage of 20 kV. Meanwhile, the base, middle and end line voltage profiles are based on simulation results, the installed load conditions produce a base voltage level of 19.77kV with a voltage drop of 1.2%, the middle of the line 19.09kV with a voltage drop of 3.3% and the end of the line 18.907kV with a voltage fell by 4.3%. Repairing the line voltage profile using capacitor banks on lines and buses that experience voltage drops, namely on BusL-ERIE3 of 2x400 kVAR, is able to improve the voltage profile at the base of the line by 19.804kV or 99%, the middle of the line 19.24kV or 96.2% and the end 19,074kV line or 95.4%.

Downloads

Download data is not yet available.

References

Malvin Jati Kuncara Alam, R.F.F. (2022) ‘Kerja Sama Operasi Penyediaan Listrik di Indonesia Bagian Timur: Harapan dan Hambatan’, CONSTITUTUM Jurnal Ilmiah Hukum, 1(1), pp. 86–99.

Kementerian Energi dan Sumber Daya Mineral Direktorat Jenderal Ketenagalistrikan, “Statistik Ketenagalistrikan Tahun 2022,” Stat. Ketenagalistrikan 2022, vol. Edisi No., 2023.

Setiawan, Wawan Randi Adzin Murdiantoro, N. (2021) ‘Analisis Keandalan Sistem Distribusi Tenaga Listrik Akibat Gangguan pada Masa Pandemi COVID-19 di PT. PLN (Persero) ULP Sidareja’, Journal of Electronic and Electrical Power Application, p. 1.

R. Duyo, “Analisis Penyebab Gangguan Jaringan pada Distribusi Listrik Menggunakan Metode Fault Tree Analysis,” J. Tek. Elektro UNISMUH, vol. 12, no. 2, pp. 1–12, 2020, [Online]. Available: https://journal.unismuh.ac.id/index.php/vertex/article/view/4017

C. Rochman, O. Penangsang, and N. K. Aryani, “Manajemen Gangguan Jaringan Distribusi 20 kV Kota Surabaya berbasis Geographic Information System (GIS) menggunakan Metode Algoritma Genetika,” J. Tek. ITS, vol. 6, no. 1, pp. 51–56, 2017, doi: 10.12962/j23373539.v6i1.21304.

Marceau A F Haurissa, “SIMULASI ALIRAN DAYA BERBASIS ETAP MENGGUNAKAN METODE NEWTON RAPHSON PADA JARINGAN DISTRIBUSI 20KV PENYULANG LATERI 2 DAN LATERI 3,” J. ELKO (Elektrikal dan komputer), vol. 4, no. 1, pp. 360–368, 2023.

M. A. Sobikin, “Analisis Drop Tegangan dan Manuver Jaringan pada Penyulang SGN11 dan Penyulang SGN14 Menggunakan Software ETAP 16.0.0,” Cyclotron, vol. 5, no. 1, 2022.

I. Kartika Pebrianti, A. Azis, N. Nurdiana, and Y. Irwansi, “Analisa Jatuh Tegangan pada Penyulang Cendana Gardu Induk Bungaran Palembang,” J. Ampere, vol. 6, no. 2, pp. 1–3, 2021, [Online]. Available: http://doi.org/10.31851/ampere

Y.- Marniati, “Analisis Penambahan Jurusan Gardu Distribusi I.598 Pada Penyulang Apel Pt.Pln Rayon Rivai Palembang,” J. Tekno, vol. 19, no. 2, pp. 32–48, 2023, doi: 10.33557/jtekno.v19i2.1911.

P.A.Wicaksono,“Analisis Tegangan Jatuh Pada Unit Kilang Di Pusat Pengembangan Sumber Daya Manusia Minyak Dan Gas Bumi Cepu Berbasis Etap 12.6.0,”J.Tek. Elektro, vol.10, no.2, pp.473–483, 2021.

Sobikin, M.A. (2022) ‘Analisis Drop Tegangan dan Manuver Jaringan pada Penyulang SGN11 dan Penyulang SGN14 Menggunakan Software ETAP 16.0.0’, Cyclotron, 5(1). Available at: https://doi.org/10.30651/cl.v5i1.10638.

Erhaneli, Z. Anthony, S. Amalia, and H. F. P. Sari, “Perbaikan Nilai Susut Teknis Jaringan Tegangan Menengah Penyulang 5 Matur PT PLN Rayon Koto Tuo,” J. Tek. Elektro Inst. Teknol. Padang, vol. 9, no. 2, pp. 67–71, 2020, [Online]. Available: https://ejournal.itp.ac.id/index.php/telektro/index

J. P. Ulahayanan et al., “Studi Perbaikan Kualitas Tegangan Pada Jaringan Distribusi Primer 20 kV di Kota Gorontalo,” Tek. Elektro dan Komput., vol. 8, no. 2, pp. 93–102, 2019.

I. Widihastuti and D. Nugroho, “Analisa Drop Tegangan Pada Feeder K3 Gardu Induk Kota Kabupaten,” J. Transistor Elektro dan Inform. (TRANSISTOR EI, vol. 4, no. 3, pp. 208–2017, 2022.

Widihastuti, I. and Nugroho, D. (2022) ‘Analisa Drop Tegangan Pada Feeder K3 Gardu Induk Kota Kabupaten’, Jurnal Transistor Elektro dan Informatika (TRANSISTOR EI, 4(3), pp. 208–2017.

Published
2024-03-29
How to Cite
A. F. Haurissa, M., Jamlaay, M., & Parera, L. M. (2024). Evaluation of Voltage Profile in ETAP (Electric Transient And Analysis Program) at Ahuru Feeder 20 kV Medium Voltage Distriution. International Journal of Science, Technology & Management, 5(2), 460-466. https://doi.org/10.46729/ijstm.v5i2.1066
Section
Articles